» Four Zone Annunciator
Alarm Panel : AR4
The AR4 Alarm Repeat Module is a four zone miniature Repeat Alarm
Unit designed to provide remote audio-visual alarms from any
monitored source which is fitted with alarm signalling 'clean
no-volt' relay/s. Can be sized for the specific number of zones
required.
The AR4 Module requires to be powered from a local external mains
supply and uses a low voltage signal link to connect to the
monitored source. Each zone is provided with audible and visual
alarms via zone LED Alarm Indicators, an internal Sounder and an
external Mute Button.
A Leader Cable would connect the Controller to the alarm source and
should be connected to 'normally open' no-volt contact in the alarm
source. When contacts within the alarm source close, the light on
the AR4 activates. The light remains on all the time that the alarm
source remains in alarm. The horn sounds, and can be muted by
pressing the Mute Button.
AR4 Module is fully self re-setting on acknowledgement of the horn
and requires no further operator re-set. The horn automatically
reactivates after any previous muting operation.
The AR4 Module can be used to provide onward signalling when fitted
with the optional 'No-Volt' output signalling relays (rated 240VAC
2amp) with 'Normally Open/Closed' change-over contacts. This can be
used to link to a secondary Repeat Alarm Modules or to link to a BMS
System.
|
 |