» BREEAM Water Leak Detection System [Type
WG]
The Aqualeak BREEAM WG 'in-pipe' Water Leak Detection System was
specifically designed to meet and exceed the Building Research
Establishment's BREEAM Credit Criteria assessment applications, W02 and W03, and will
qualify for the granting of the "Credit Point". These
criteria are specified for energy efficient buildings where water
leak detection is required between the property boundary and the
building, and internally within the building. The system is designed
to monitor water flowing through the incoming water pipe and if the
amount goes beyond the adjustable pre-set limit this product will
raise an alarm and [optionally] shut off the water supply.
Similarly, our AquaPIR
Systems will shut off the water supply in the
washrooms to conform to BREEAM criteria W04.
The system comprises of a two-zone WG2 Control Unit which would be
linked to two turbine sensors. The first turbine would be fitted
just after the utilities water meter and would monitor the water
pipe external to the building. The second turbine would be fitted
just after the stop-cock inside, and would monitor for leaks within
the building. The turbines provide a 'pulse' as water flows through
them. Should the adjustable pre-set
quantity of pulses/litres be exceeded, the WG system would provide
local audio-visual alarms, and the output relay/s would provide a
signal to remote alarms or BMS. If required, the system can also shut off the water
supply via the optional solenoid valve/s.
The system is fully programmable to detect different leakage rates
over set time periods. As the building may be occupied during the day and as the water
usage may be constant, the Controller is also provided with an
integral timer that can be set so that the System would operate only
in 'out-of-hours' periods. The system can then either turn off the
water completely at say 6pm, or can be set to alarm/shut off water
on the basis of a quantity of water flowing through the Meter.
WG Systems are available to suit a wide range of industrial pipe
sizes: 15, 22, 25, 30, 40, 50, 65, 80, 100, 150 and 200mm (imperial 1/2" to
8").
Single zone WG1 System (shown left) would be used in non-BREEAM applications requiring
monitoring of a domestic incoming water supply into the building,
for local monitoring of specific area/s and for providing individual
shut-off facilities. Smaller domestic systems suitable for 15,
22 and 28mm are also available, with flow sensors rather than
turbines, and with simpler more economical control systems. Domestic
systems are widely used to monitor flats and houses and to shut off
the water if a leak occurs.
|
 |